Optimization of active power filter current for selected bus of power supplying network
The paper presents results of optimization of active power filter (APF) parameters connected to a selected bus of a power supplying network. In the optimization process power filter currents are minimized with respect to voltage harmonic distortions (THDV) at the APF connection bus. Results showed, that the APF parameters significantly change not only the THDV on the connection bus but also on the other system busses. Simulation has been performed using Matlab and PCFLO software.
"Dorobek" bibliographic database - record no. 0000080849 ; oai:delibra.bg.polsl.pl:29905
Oct 2, 2015
Sep 30, 2015
147
https://delibra.bg.polsl.pl/publication/34083
Edition name | Date |
---|---|
OPTYMALIZACJA PRĄDU ENERGETYCZNEGO FILTRU AKTYWNEGO DLA WYBRANEGO WĘZŁA SIECI ZASILAJĄCEJ | Oct 2, 2015 |
Walczak, Janusz Lewandowski, Michał
Walczak, Janusz Lewandowski, Michał
Buła, Dawid Grabowski, Dariusz Lewandowski, Michał Maciążek, Marcin Pasko, Marian Piwowar, Anna Walczak, Janusz
Maciążek, Marcin Pasko, Marian Komitet Elektrotechniki. Polska Akademia Nauk
Grabowski, Dariusz Maciążek, Marcin Pasko, Marian
Piwowar, Anna Walczak, Janusz. Promotor Mikołajuk, Kazimierz. Recenzent Pasko, Marian. Recenzent